Plan
104 OSOEOLA RD, WOODLAND PARK, CO 80863
County Parcel #: 2943.012020540
Roof Truss P/SF: ?
PROJECT: RESIDENCE (
101
)
Submit Date
Approval Date
Type of Plan: Normal
Review Type: Parallel
Plan Image
View Plan Image
Download Plan Image
Map
Google Map
Yahoo Maps
Bing Maps
MapQuest
County Map & Data
PPRBD Directions
Path 1 Location
Path 2 Location
Details
View
Log
Time Summary
Required Departments: 5
Log Entries: 7
Department
S
BoundColumn_2
Department
Construction
D
C
Construction
Env. Health
/
H
Env. Health
Floodplain
A
W
Floodplain
Triage
N
J
Triage
County Zoning
A
Z
County Zoning
Department
Splice
S
Date
Inspector
Reviewer
Comment
username
Department
tid
Construction
Original
D
10/6/2021
HARTSFIELDK
HARTSFIELDK
1. Provide log details to address differential settlement. (Windows Doors, Interior walls) or provide documentation explaining why differential settlement is not an issue (log size, species, moisture content) (IRC 301.1.1 - ICC Standard 400)
2. A minimum 6’-8” headroom is required at the intermediate stair landing. Adjust stairs as necessary.
3. Provide header information for interior bearing walls.
4. Call out roof framing above kitchen /bedroom #2 (rafter size spacing and species, collar ties, rafter ties?)
5. The revised drawings are missing the stamp of a licensed design professional as required by TCBC R602.3.
Construction
31263
Construction
Original
D
9/24/2021
HARTSFIELDK
HARTSFIELDK
1. Provide log details to address differential settlement. (Windows Doors, Interior walls)
2. Roof framing plan calls for bearing walls in the loft. These are not shown in the loft plan nor section. Coordinate drawings.
3. Confirm 6’-8” min stair headroom at exterior wall at intermediate landing.
4. Minimum stair tread depth is 10” per IRC 311.7.5.2 revise stairs in plan and section
5. Clarify how the rafters attached to log walls.
6. Clarify header requirements in log walls.
7. Provide header information for interior bearing walls.
8. Call out roof framing above kitchen (rafter size spacing and species)
9. Call out size of ridge rafters.
Construction
31149
County Zoning
Original
A
9/20/2021
CORCORANC
CORCORANC
SITE PLAN SURVEY SUBMITTED
County Zoning
31071
Triage
Original
N
9/20/2021
CORCORANC
CORCORANC
emailed for soils report to homeowner
Triage
31062
County Zoning
Original
D
9/20/2021
CORCORANC
CORCORANC
NEED SIGNED SITE PLAN FROM SURVEYOR
County Zoning
31061
Floodplain
Original
A
9/20/2021
CORCORANC
CORCORANC
FEMA MAP # 08119C0208D
Floodplain
31060
Triage
Original
N
9/20/2021
CORCORANC
CORCORANC
DRIVEWAY IS ON A59678
Triage
31059