| Construction | Original | A | 10/14/2024 | SNYDERJ | SNYDERJ | APPROVED - JS | | Construction | 40496 |
| Construction | Original | D | 9/13/2024 | HOEKMANL | HOEKMANL | 1) Provide one complete set of plans with all previous corrections addressed. There have been too many revisions to accept page by page individual submittals. Once we have the complete up-to-date stamped set of plans we will complete your plan review. | | Construction | 40170 |
| Env. Health | Original | / | 9/13/2024 | SNYDERJ | SNYDERJ | In Current Review by SNYDERJ | | Env. Health | 40169 |
| Construction | Original | D | 9/11/2024 | BLACKBURNL | BLACKBURNL | PLAN CORRECTIONS (entitled 56 Camelback Lane-2024-09-01.pdf) UPDATED TO R17042 "REV PLAN 9-1-24" FOLDER; EMAIL TO JS FOR REVIEW OF REVISED PLANS TO APPROVE R17042 Construction Department. Email to JS for review/approval. | | Construction | 40128 |
| Env. Health | Original | A | 8/15/2024 | MAYA | MAYA | Approved. | | Env. Health | 39905 |
| Env. Health | Original | D | 8/13/2024 | MAYA | MAYA | Application not complete. Waiting on response from owner. | | Env. Health | 39867 |
| Env. Health | Original | / | 8/13/2024 | MAYA | MAYA | Path 1 Location = Env. Health by MAYA | | Env. Health | 39866 |
| Construction | Original | D | 8/9/2024 | STEINM | STEINM | 1) The design criteria for wind load not listed. Teller County is 115 mph (vult) minimum. 2) What type of heat? A heat source to provide 68 degrees with thermostat control is required. 3) Show location of appliances, electrical panel and disconnect. 4) Exterior deck framing – What type of lumber? Show ledger attachment per R507. Show post to beam attachment. | | Construction | 39823 |
| Construction | Original | D | 8/2/2024 | STEINM | STEINM | • THE PLANS SENT ON 8/1/24 DO NOT HAVE CORRECT ADDRESS AND HAVE A COPYRIGHT PROTECTION AND CANNOT BE USED. | | Construction | 39744 |
| Env. Health | Original | D | 8/1/2024 | HOEKMANL | HOEKMANL | DESIGN PLANS PROVIDED - TEAMS TO EH 8/1/2024 | | Env. Health | 39713 |
| Construction | Original | D | 6/28/2024 | STEINM | STEINM | • NEED CURRENT IECC FORM FOR THE 2018 ENERGY CODE. RES CHECK APPROVED 6/28/24 • NEED ENGINEERED STRUCTURAL PLANS TO HAVE CORRECT DESIGN CRITERIA. ROOF LIVE (SNOW) LOAD IS MIN. 40 P.S.F. – GROUND SNOW LOAD IS MIN. 57 P.S.F. – WIND LOAD IS 115 M.P.H. ULTIMATE – THE FOUNDATION DESIGN NEEDS TO BE FOR A 1500 P.S.F. MAXIMUM ALLOWABLE BEARING PRESSURE, PER SOILS REPORT. • THERE NEEDS TO BE A 36” SIDE HINGED DOOR TO GRADE LEVEL, R311.2 • THE PLANS SENT ON 2/22/24 WERE NOT SIZED CORRECTLY. THE RIGHT HALF OF PAGES 1 THROUGH 3 ARE MISSING. NEED COMPLETE SET. NEED IECC FORM. NEED A 36” SIDE HINGED DOOR TO GRADE LEVEL. • THE PLANS SENT ON 2/2/24 WERE NOT SIZED CORRECTLY. PLEASE SEND A LEGIBLE COPY OF PLANS. | | Construction | 39441 |
| Env. Health | Original | D | 6/26/2024 | MAYA | MAYA | Application not complete. Design in L: drive is not for this property. Need correct design. | | Env. Health | 39403 |
| Construction | Original | D | 6/26/2024 | BLACKBURNL | BLACKBURNL | 2/22/2024 PLANS REV 2 received. 6/26/2024 CHANGE OF CONTRACTOR received - Change HO to Premier Consulting & Construction | | Construction | 39397 |
| Env. Health | Original | D | 6/24/2024 | HOEKMANL | HOEKMANL | NEED SEPTIC DESIGN | | Env. Health | 39360 |
| Construction | Original | D | 2/22/2024 | STEINM | STEINM | DENIED ON 2/22/24 | | Construction | 38498 |
| Env. Health | Original | / | 2/21/2024 | HOEKMANL | HOEKMANL | TEAM TO EH 2/21/2024 | | Env. Health | 38483 |
| Triage | Original | A | 2/14/2024 | HOEKMANL | HOEKMANL | SEPTIC APPLICATION RECEIVED - STILL NEED PAYMENT | | Triage | 38455 |
| Construction | Original | D | 10/27/2023 | STEINM | STEINM | • NEED CURRENT IECC FORM FOR THE 2018 ENERGY CODE. • NEED ENGINEERED STRUCTURAL PLANS TO HAVE CORRECT DESIGN CRITERIA. ROOF LIVE (SNOW) LOAD IS MIN. 40 P.S.F. – GROUND SNOW LOAD IS MIN. 57 P.S.F. – WIND LOAD IS 115 M.P.H. ULTIMATE – THE FOUNDATION DESIGN NEEDS TO BE FOR A 1500 P.S.F. MAXIMUM ALLOWABLE BEARING PRESSURE, PER SOILS REPORT. • THERE NEEDS TO BE A 36” SIDE HINGED DOOR TO GRADE LEVEL, R311.2 | | Construction | 37913 |
| Construction | Original | D | 8/16/2023 | STEINM | STEINM | PLAN SUBMITTAL DOES NOT MEET REQUIREMENTS:
• SHEETS 1,2 AND 3 DO NOT MATCH ENGINEERED FOUNDATION PLAN. NEED CORRECT FLOOR PLAN, ELEVATIONS TO MATCH ENGINEERING. • NEED DESIGN CRITERIA ON ENGINEERED STAMPED PLANS (WIND, SNOW, ETC.) . THE FROST PROTECTION IS 30 INCHES MINIMUM. • NEED CURRENT IECC FORM FOR 2018 IECC. | | Construction | 37174 |
| County Zoning | Original | A | 8/14/2023 | MCBRYDEJ | MCBRYDEJ | Approval has been granted based on adherence to setback regulations and the provision of a legally compliant description. | | County Zoning | 37139 |
| Triage | Original | A | 8/10/2023 | HOEKMANL | HOEKMANL | NEED SEPTIC APPLICATION
DRIVEWAY ON PERMIT A62992
BRYANDNELSONJR89@GMAIL.COM | | Triage | 37113 |
| Floodplain | Original | A | 8/10/2023 | HOEKMANL | HOEKMANL | FEMA MAP # 08119C0190D | | Floodplain | 37112 |