HOMEOWNER | B= | C | 07/06/2015 | INSPECTIONS AND FILE COMPLETE | CORCORANC | CORCORANC | | B= | C | 196859 |
HOMEOWNER | BFR | C | 07/02/2015 | bath fan inspected | HARRISJ | HARRISJ | | BFR | C | 196857 |
HOMEOWNER | B= | P | 05/29/2015 | Additional Inspections Required: Certificate of Occupancy is pending review by CDSD staff. Floodplain Final Inspection is not Completed yet, Electrical Final Inspection is not Completed yet. | HARRISJ | HARRISJ | | B= | P | 196131 |
HOMEOWNER | BE | P | 05/26/2015 | Renewed at 5/26/2015 9:25:09 AM | BRUNETTET | BRUNETTET | | BE | P | 196082 |
HOMEOWNER | BIN | C | 07/11/2014 | | HARRISJ | HARRISJ | | BIN | C | 191485 |
HOMEOWNER | BIN | P | 06/27/2014 | kitchen,pantry, and both bathrooms | HARRISJ | HARRISJ | | BIN | P | 191288 |
HOMEOWNER | BSP | C | 05/29/2014 | FIRST EXTENSION GRANTED FROM 8.24.13. TO 8.24.14. ---OS | SHARONOVAO | SHARONOVAO | | BSP | C | 190719 |
HOMEOWNER | BFR | P | 05/29/2014 | need electric rough for baseboard heaters need bath fan inspected decks not complete at this time ok to insulate after electric rough for baseboards has been inspected need front door cover completed | HARRISJ | HARRISJ | | BFR | P | 190731 |
HOMEOWNER | BPR | C | 05/29/2014 | 3 each | HARRISJ | HARRISJ | | BPR | C | 190736 |
HOMEOWNER | B16 | C | 08/27/2013 | EXTENSION GRANTED - PERMIT EXPIRATION IS 8/242013----no extension was needed---o.s. | CORCORANC | CORCORANC | | B16 | C | 186119 |
HOMEOWNER | BGF | C | 10/16/2012 | need verification about fastners that were used and a change order to add 2 extra windows on front wall | HARRISJ | HARRISJ | | BGF | C | 180161 |
HOMEOWNER | BUL | C | 10/09/2012 | | LANDSITTELM | LANDSITTELM | | BUL | C | 180011 |
HOMEOWNER | BSH | C | 10/05/2012 | | HARRISJ | HARRISJ | | BSH | C | 179906 |
HOMEOWNER | BSH | P | 09/26/2012 | RAINING ROLLED OVER 09-26-12 wall and SIP roof panels ok, will have one more roof inspection due to design | LANDSITTELM | LANDSITTELM | | BSH | P | 179636 |
HOMEOWNER | BSP | C | 09/18/2012 | This is a foundation drain for the addition with the change order per Mr. Sutcliff | LANDSITTELM | LANDSITTELM | | BSP | C | 179419 |
HOMEOWNER | BPR | P | 08/28/2012 | 6 piers north and south deck | HARRISJ | HARRISJ | | BPR | P | 178937 |
GENE'S FOUNDATION CO | BFN | C | 08/15/2012 | | HARRISJ | HARRISJ | | BFN | C | 178661 |
HOMEOWNER | BFT | C | 08/10/2012 | THIS IS FOR CHANGE ORDER FOOTING | LANDSITTELM | LANDSITTELM | | BFT | C | 178577 |
HOMEOWNER | BFD | C | 09/30/2011 | | LANDSITTELM | LANDSITTELM | | BFD | C | 172998 |
HOMEOWNER | BFN | C | 09/06/2011 | Open hole on site | LANDSITTELM | LANDSITTELM | | BFN | C | 172294 |
HOMEOWNER | BFT | P | 08/26/2011 | | HARRISJ | HARRISJ | | BFT | P | 172054 |
HOMEOWNER | E= | C | 05/29/2015 | All issues resolved. dlw | WILSOND | WILSOND | | E= | C | 196141 |
HOMEOWNER | E= | R | 05/27/2015 | Issues with fan in shower, light in two showers, outlets for lights in basement, AFCI for bedroom lighting, metal box on EMT . dlw | WILSOND | WILSOND | | E= | R | 196108 |
HOMEOWNER | ER | C | 06/30/2014 | For Electric Heat and corrections, dlw | WILSOND | WILSOND | | ER | C | 191329 |
HOMEOWNER | ER | P | 05/28/2014 | Check these things at final elect. all BR circuits to be AFCI, Floor outlet at railing in loft, light in bath off 20 amp circuit, Dryer to be four wire set up, cord and plug, move wires too close to stud edges. dlw | WILSOND | WILSOND | | ER | P | 190705 |
HOMEOWNER | ER | R | 09/24/2013 | Not ready, boxes not in place,smokes not in place,circuiting not correct. dlw | WILSOND | WILSOND | | ER | R | 186716 |
HOMEOWNER | ES | C | 10/19/2011 | Residential Overhead: This service is already hooked up as a temporary for construction, Meter #55 218 564 . dlw | WILSOND | WILSOND | | ES | C | 173503 |
HOMEOWNER | EUG | C | 10/19/2011 | | WILSOND | WILSOND | | EUG | C | 173502 |
HOMEOWNER | FP= | C | 07/01/2015 | | CORCORANC | CORCORANC | BDA | FP= | C | 196801 |
HOMEOWNER | H= | C | 05/29/2015 | | HARRISJ | HARRISJ | | H= | C | 196129 |
HOMEOWNER | H= | P | 05/29/2014 | check forRADIANT IN BASEMENT AND ELE MAIN FLOOR at B= | HARRISJ | HARRISJ | | H= | P | 190730 |
HOMEOWNER | HFV | C | 05/29/2014 | | HARRISJ | HARRISJ | | HFV | C | 190729 |
HOMEOWNER | HFF | C | 05/29/2014 | check at B= | HARRISJ | HARRISJ | | HFF | C | 190728 |
ROBLES EXCAVATING | OS= | C | 09/06/2013 | | DOUSSETTA | DOUSSETTA | | OS= | C | 186361 |
ROBLES EXCAVATING | OE | P | 09/05/2013 | Renewed at 9/5/2013 12:17:31 PM | CORCORANC | CORCORANC | | OE | P | 186324 |
ROBLES EXCAVATING | OSPT | C | 10/19/2011 | connection to basement. still need connection to upper level of house for final approval. | DAHLK | DAHLK | | OSPT | C | 173505 |
HOMEOWNER | P= | C | 05/29/2015 | | HARRISJ | HARRISJ | | P= | C | 196130 |
HOMEOWNER | PTO | C | 08/27/2013 | | HARRISJ | HARRISJ | | PTO | C | 186100 |
HOMEOWNER | PB | C | 09/22/2011 | | HARRISJ | HARRISJ | | PB | C | 172742 |
HOMEOWNER | PB | R | 09/19/2011 | Vent toilet, no san tees for horizontal drains,washer drain 6' to 3" | LANDSITTELM | LANDSITTELM | | PB | R | 172633 |